Machinery requirements
It is a standard requirement that all propulsion and auxiliary
machinery fitted should be capable of operating when upright and when inclined
at an angle of list up to 15o either way under static conditions and 22 ½o
under dynamic conditions either way and when simultaneously inclined
dynamically 7 1/20 by bow and stern. The emergency generating sets shall be
capable of functioning when the ship is inclined 22 1/2o from upright and
inclined 100 bow to stern. The two main factors of concern are lubrication and
the functioning of contactors, switchgear and relays having unsymmetrical or
unbalanced magnetic systems when the magnetic pull required to operate
increases with tilt. Apparatus, such as transformers or switches, containing
oil could be affected.
Temperature effects
Extremes of temperature will affect the performance and the
effective life of the electrical apparatus. Devices which depend on
electromagnetic operation by shunt coils will find resistance of the coil
increases with temperature so with less current both the ampere turns and the
field strength is reduced.
Contactors
and relays may fail to operate correctly if overheated.
The
total temperature is determined partly by ambient air temperature and partly by
heating effect of the current windings.
This
heating effect gives a temperature rise and this is always about the same for
similar load.
The
total temperature, which will affect the life of the insulation and the
performance of the equipment, will be maximum at the maximum ambient
temperature. For unrestricted service the cooling air temperature is 45oC
. For restricted service and vessels intended for northern and southern waters
outside of the tropical belt the temperature is 40oC.
Adequate
ventilation and avoidance of hot pockets where electrical apparatus operates is
important.
When
considering suitable operating temperature for a device the 'hot spot
temperature' is important. In the field coil the hot spot is somewhere in the
centre of the winding and there is a temperature gradient form there to the
surface. Previous recorded surface temperature values corresponding to
specified hot spots temperature are acceptable for recording the machines
performance. Another method is to record changes in resistance due to
temperature in the winding.
Installation and
maintenance
To reduce end play and avoid hammering
during rolling machines should be installed with their axis of rotation in the
fore and aft direction or vertically. If unavoidable that the machine is placed
athwartships suitable thrust bearings should be provided against the hammering
effect. Special attention should be paid to the lubrication of ring lubricated
sleeve bearings.
The main cause of overheating in
electrical joints is loose connections usually due to vibrational problems. All
screws and nuts should be locked and periodically checked and tightened if
necessary.
Heavy current circuits, control and shunt
field circuits should all be checked.
Machine rating
The recognised standard is the Continuous maximum rating (C.M.R.),
motors and generators are seldom if ever called upon to operate under sustained
overload.
Momentary
overloads (15s for test purposes) of 50% in generators is allowed. Motor
overload is determined by function and size.
C.M.R. machines will still carry moderate
overloads for reasonable duration's. An example of this may be an oil pump on
start up may experience high loads as the oil is initially cold. Circuit protection
For
example;
- Motor drawing 100A on 220v supply 218v measured
at motor terminals giving a 2 volt drop across cables
- Cable resistance therefore is 0.02 Ohm's.
If the motor is bypassed the PROSPECTIVE
SHORT CIRCUIT current would be 11,000A
The main circuit breaker may be protected
by fuses or a circuit breaker having at least the necessary breaking capacity
and fast enough operative time. This is 'back up' protection. Generator circuit
breakers must not be used for this purpose.
In motor circuits the breaking capacity of
motor starters is usually very limited and does not greatly exceed the starting
current of the motors, If a fuse is fitted for 'back up' protection of the
motor starter it should be able to carry the starter current for the time
necessary to start the motor plus a suitable margin. If correctly chosen it
will not blow except under maximum mechanical fault or electrical fault or
overload conditions. It will still give protection should the fault current
exceed what the motor starter can handle.
If A.C. generators and their excitation
systems undergo steady short circuit conditions they should be capable of
maintaining a current of at least three times its rated value for 2 seconds
unless requirements are made for a shorter duration. The safety of the
installations must be insured.
Performance
The standard condition for generator performance is based on the
starting kVA of the largest motor, or group of motors which can be started
simultaneously and this kVA should not exceed 60% of the generator capacity.
Voltage
should not fall below 85% or rise above 120% of the rated voltage when such a
load have a power factor from zero to 0.4 is thrown on or thrown off the board.
Voltage
must be restored to within 3% of the rated voltage within 1.5s. For emergency
generators 4% in 5s is allowed. The transient effect when a load is suddenly
thrown on is to cause a voltage dip. This dip may be made less if the generator
is designed to have a lower reactance during transient conditions. However, too
low a reactance with a smaller voltage dip may involve high short circuit
currents in excess of capabilities of the available protective devices.
The
designer must consider the opposing conditions of low transient voltage dip and
low short circuit currents and balance these conditions against possible
increase in machine size, weight and cost.
IMPORTANT REQUIREMENTS FOR ELECTRICAL MACHINARY
Reviewed by HODO
on
September 22, 2017
Rating: