AUXILIARY BOILER STARTING PROCEDURES
BOILER MODE:
This mode is selected when tanker cargo operations are required.
In Boiler mode: BOILER AUTO ON @
1.52Mpa
BOILER AUTO OFF @ 1.67Mpa
ECONOMIZR MODE:
This mode is selected at normal sea going (Economizer Back up)
Condition
In ECO Mode: BOILER AUTO
ON @ 0.44Mpa
BOILER
AUTO OFF @ 0.59 Mpa
IGS MODE:
This Mode is selected at inert gas topping up operation.
PROCEDURES FOR STARTING BOILER
-
Two generators
to run (As per load condition)
-
Control Source ON.
-
Flame Eye –
Bypass Normal.
-
Thermostat
bypass ON/OFF depending on oil.
-
Oil Heater
ON/OFF depending on oil.
-
Fuel oil temp
around 110 Deg.C if HFO.
-
Main Feed P/P to
change over whenever blr press above 1 Mpa.
Auto Operation:
Starting:
-
Depending on
requirement select boiler mode or EGB mode.
-
Confirm all are
in auto mode.
-
Boiler
operations switch auto to auto on position and release.
-
Primary /
Secondary / Burner motor start in auto sequence.
-
Pre-purge
sequence @ 30 secs
-
Ignition takes
place @ 3 secs.
-
Main valve on
(FO)
-
Combustion
starts after flame eye senses the flame.
Stopping:
-
Burner Operation
Stop.
-
DO mixing
sequence if HO burning in the burner @ 15 secs.
-
Stop.
-
Post Purge
sequence @ 30 secs.
-
After primary /
secondary / Burner motor stops @ 30 Mins